Home / Nurse call / Duress alarms in hospitals

Nurse call · engineering note · 22 November 2026

Duress alarms in hospitals: requirements, escalation and integration.

A duress alarm lets a staff member call for help without the aggressor knowing. Getting one into a hospital is the easy part. Making sure every press reaches someone who comes, every time, across nurse call, phones, cameras and doors, is where most systems fall short. This note covers what applies in Australia, how to design the escalation, and how to integrate it without creating silent failure points.

Planning or fixing a duress system?

Talk to Peninsula Smart Care, our installation partner. They design, install and maintain duress alarm systems for healthcare facilities.

Call 03 7504 7011Duress alarm systems →

Support in Melbourne

Peninsula Smart CareOur installation partner, based in Cheltenham. Designs, installs and maintains duress alarm systems for healthcare facilities, integrated with nurse call, access control and RTLS, supporting facilities Australia-wide.

What a duress alarm has to do

Requirements in Australia

Healthcare security in Australia is guided by AS 4485:2021 Security for healthcare facilities, published in two parts: AS 4485.1 General requirements and AS 4485.2 Procedures guide. It isn't law on its own. A standard binds a facility only where legislation, health service policy or a contract calls it up. In Victoria the enforceable duty sits in the Occupational Health and Safety Act 2004, which requires employers to provide and maintain a working environment that is safe so far as is reasonably practicable.

Hospital emergency colour codes come from AS 4083 Planning for emergencies: Health care facilities. In Victoria, Code Grey is the response to unarmed aggression and Code Black to an armed threat, but the labels differ between states, so a duress system has to match the codes and escalation paths your facility actually runs.

Fixed and wearable duress points

Most facilities need both. Fixed points, under the desk or on the wall, suit reception, triage, interview and treatment rooms, where staff are in a known place. Wearable points, pendants or badges, suit staff who move between rooms, wards and car parks. A wearable is only as useful as the location behind it: without a way to place the wearer, an alert says "someone needs help" but not where.

Designing the escalation process

The escalation path is the system. Write it down before choosing hardware:

  1. First response. Who is alerted the moment a button is pressed: usually nearby staff and security together.
  2. Acknowledgement. How a responder accepts the alert, so others know help is on the way.
  3. Timeout. How long before an unacknowledged alert escalates, and to whom: the switchboard, a wider group, or a Code Grey call.
  4. Resolution. How the alert is cleared, by whom, and what is recorded.
  5. Review. Every press, acknowledgement and escalation logged with times, for incident review and for showing the system works.

Integrating with hospital infrastructure

Every link between systems is another place an alert can be lost. Each one should be supervised, so a dropped link raises a fault instead of failing silently.

Supervision and testing

Duress systems fail silently. A flat pendant battery, a receiver knocked off channel, or an under-desk button whose cable was cut during a fitout doesn't report itself. Test every device on a written schedule and record the result against the device's ID rather than the room, so a missed device shows up in the record instead of disappearing into a ward-level tick.

A quick checklist

Questions we get asked

Is a duress alarm system required in Australian hospitals?

No single law names a duress system, but the duty is real. In Victoria the Occupational Health and Safety Act 2004 requires employers to keep the workplace safe so far as is reasonably practicable, and AS 4485:2021 Security for healthcare facilities is the standard health services use to show how. AS 4485 binds a facility only where legislation, policy or a contract calls it up.

What should a duress alarm escalation process look like?

Write it down before you choose hardware: who is alerted first, how they acknowledge, how long before it escalates, and to whom. A typical path alerts nearby staff and security at once, escalates to the switchboard or a Code Grey call if nobody acknowledges, and logs every step for review.

Should duress alarms be wearable or fixed?

Usually both. Fixed under-desk and wall buttons cover reception desks, interview rooms and treatment rooms. Wearable pendants or badges cover staff who move between areas, and only help if the system can tell responders where the wearer is.

How does a duress alarm integrate with hospital systems?

The alert should reach staff on the displays and phones they already carry for nurse calls, call up the nearest camera, and where policy allows, trigger door lockdowns through access control. Every integration point is another place a message can be lost, so each one needs to be supervised.

How often should duress alarms be tested?

On a written schedule, device by device, with the result recorded against each device's ID rather than the room. Duress devices fail silently: a flat pendant or a cut cable only shows up when someone presses it.

Need a duress system designed, upgraded or tested?

Send the facility type, the number of areas and what runs nurse call today. Peninsula Smart Care will walk the site and quote it in writing.

Call 03 7504 7011Duress alarms at Peninsula Smart Care →

Support in Melbourne

Peninsula Smart CareOur installation partner, based in Cheltenham. Designs, installs and maintains duress alarm systems for healthcare facilities, integrated with nurse call, access control and RTLS, supporting facilities Australia-wide.