XM-02 — PoE module Available now
Eight relays and eight inputs, powered and connected by one PoE Ethernet cable. Put it where the lights and contacts are — a corridor cabinet, a staff base, a duress point — with no bus or power run. It is the Edge Node hardware running in expansion mode, paired to a parent node.
- Expansion inputs are call inputs. Each expander input gets its own call type, contact sense and label on the parent, and routes to relays, the Axis speaker, clinical messaging and the ward display exactly like an onboard input. Inputs are sampled every 20 ms and latched until the parent has read them, so a short press is never lost.
- Two paths, supervised. The parent polls the expander over Ethernet and fails over to a two-wire RS-485 link within two seconds if the network path dies, then back again, logging every change. If the expander loses the parent on both paths it applies a defined relay state — hold or all-off, your choice — and logs the loss. How Southerly stays up →
- Fast. A duress button on an expander input reaches the ward board in well under a second.
- Secured. Expander commands carry a shared key; an unauthenticated read can neither drive a relay nor mask a lost parent.
XM-01 — RS-485 module In development
The same 8 relays and 8 inputs as a bus-only DIN-rail module on the Edge Node's RS-485 port — the cheapest way to add I/O in the same cabinet or along an existing bus run. Powered from 7–36 V DC.
Node configurations
| Modules | 0 | 1 | 2 | 4 | 8 |
|---|---|---|---|---|---|
| Outputs / inputs per node | 8 / 8 | 16 / 16 | 24 / 24 | 40 / 40 | 72 / 72 |
Expansion channels appear in the node's web page, messaging rules and MQTT topics as if they were onboard, and are supervised the same way — a module that stops answering raises a fault.
Specifications
| XM-02 I/O | 8 × SPDT relay outputs (≤10 A) + 8 × opto-isolated inputs, 20 ms sampled and latched |
|---|---|
| XM-02 link | Ethernet primary (PoE 802.3af, or 7–36 V DC) with RS-485 backup; fail-over < 2 s and back; keyed commands |
| XM-02 fail-state | Relays hold or all-off if both paths are lost; loss and recovery logged on both ends |
| XM-01 I/O | 8 × relay outputs + 8 × opto-isolated inputs; RS-485 bus-only; 7–36 V DC; DIN rail |
| Per node | 1 expander per node in current firmware; 8 by design → 72 outputs / 72 inputs |
| Status | XM-02 available now (firmware 1.4.0); XM-01 in development |